6. Description of Parameters
- 144 -
6
Function Code Parameter Name Setting Range Default
F9-59
Power dip ride-through
function selection
0: Disabled
1: Bus voltage constant control
2: Decelerate to stop
0
F9-60
Threshold of power dip ride-
through function disabled
85% to 120% 85%
F9-61
Judging time of bus voltage
recovering from power dip
0.1s to 10.0s 0.5s
F9-62
Threshold of power dip ride-
through function enabled
60% to 85% (standard bus voltage) 80.0%
F9-71
Power dip ride-through gain
Kp
0 to 100 40
F9-72
Power dip ride-through
integral coefcient
0 to 100 30
F9-73
Deceleration time of power
dip ride-through
0.0s to 300.0s 20.0s
Note
In bus voltage constant control, when line voltage recovers, the AC drive
accelerates to target frequency.
In deceleration to stop mode, when line voltage recovers, the AC drive continues
to decelerate to 0 Hz and stops. The AC drive will not be started until it receives
RUN command again.
6.6.7 Load Lost Protection
Function Code Parameter Name Setting Range Default
F9-63
Load lost protection 0: Disabled
1: Enabled
0
F9-64
Load lost detection level 0.0% to 100.0% (rated motor current) 10.0%
F9-65
Load lost detection time 0.0s to 60.0s 1.0s
These function parameters dene the load lost protection function.
When output current of the AC drive falls below detection level (F9-64) for longer than time set in
F9-65, the AC drive automatically reduces output frequency to 7% of rated frequency. Once load
recovers during protection, the AC drive accelerates to frequency reference.