Command
0: No command
1: Forward run
2: Reverse run
3: Forward jog
4: Reverse jog
5: Coast to stop
6: Decelerate to stop
7: Fault reset
PLC program modified
Frequency
reference
PLC program modified
Torque
reference
PLC program modified
Fault
PLC program modified
0: No fault
80 to 89: User-defined
A7-00 = 1
Set the
programmable card
to activate.
The frequency reference is set
via communication.
For details, see section 6.2.
The running command is
given by the communication.
Set F0-02 = 2.
The frequency reference is set
via communication.
For details, see F2-09 and A0-01.
The value of A7-08 is
determined by the user
programmable card.
The value of A7-07 is
determined by the user
programmable card.
The value of A7-06 is
determined by the user
programmable card.
fault code
The value of A7-09 is
determined by the user
programmable card.
-200.0% to 200.0%
The base value of the percentage
is rated motor torque.
-100.0% to 100.0%
The base value of the percentage
is F0-10 (Max. frequency).