11. Troubleshooting
- 304 -
11
Operating Panel Display Operating Panel Display
Pulse-by-pulse current limit fault
Cause Cause
Load is too heavy or locked-rotor occurs on
motor.
Reduce load or check motor and mechanical conditions.
The AC drive power class is small. Replace a drive of larger power class.
Operating Panel Display Fault Name
Motor switchover fault during running
Cause Possible Solution
Motor switchover via terminal during drive
running of the AC drive.
Perform motor switchover after the AC drive stops.
Operating Panel Display Fault Name
Speed error
Cause Possible Solution
Encoder parameters are set improperly. Set encoder parameters properly.
Motor auto-tuning is not performed. Perform motor auto-tuning.
F9-69 (detection level of speed error) and
F9-70 (detection time of speed error) are set
incorrectly.
Set F9-69 and F9-70 correctly based on actual condition.
Operating Panel Display Fault Name
Motor overspeed
Cause Possible Solution
Encoder parameters are set improperly. Set encoder parameters properly.
Motor auto-tuning is not performed. Perform motor auto-tuning.
F9-67 (Overspeed detection level) and
F9-68 (Overspeed detection time) are set
incorrectly.
Set F9-67 and F9-68 correctly based on the actual
situation.
Operating Panel Display Fault Name
Motor overtemperature.
Cause Possible Solution
Cable connection of temperature sensor
becomes loose
Check cable connection of temperature sensor.
The motor temperature is too high. Decrease carrier frequency or take other measures to
cool the motor.
Operating Panel Display Fault Name
Braking unit overload
Cause Possible Solution
Resistance of braking resistor is too small. Replace a braking resistor of larger resistance.
Operating Panel Display Fault Name
Short-circuit of braking circuit
Cause Possible Solution
Braking module is abnormal. Contact the agent or Inovance.