Appendix. Parameter Table
- 329 -
12
Parameter
No.
Parameter Name Setting Range Default Property Page
Group A7: User Programmable Card
A7-00 User programmable function
selection
0: Disabled
1: Enabled
0
1
6
1
A7-01 AC drive output terminal control
source selection
00000 to 11111 00000
1
6
2
A7-02 User programmable card AI3 and
AO2 function selection
0 to 7 0
1
6
1
A7-03 PLC program controls the FMP
output
0.0% to 100.0% 0.0%
1
6
2
A7-04 PLC program controls the AO1
output
0.0% to 100.0% 0.0%
1
6
2
A7-05 Selection of PLC program
controlling digital output
000 to 111 000
1
6
2
A7-06 Setting frequency reference via
the user programmable card
-100.00% to 100.00% 0.00%
1
6
3
A7-07 Setting torque reference via the
user programmable card
-200.0% to 200.0% 0.0%
1
6
3
A7-08 Setting running command via the
user programmable card
0 to 7 0
1
6
2
A7-09 Setting torque reference via the
user programmable card
0: No fault
80 to 89: User dened fault
code
0
1
6
3
Group A8: Point-point Communication
A8-00 Point-point communication 0: Disabled
1: Enabled
0
1
7
0
A8-01 Master or slave selection 0: Master
1: Slave
0
1
7
0
A8-02 Selection of action of the slave in
point-point communication
000 to 111 011
1
7
1
A8-03 The slave received data 0: Output frequency
1: Frequency reference
0
1
7
1
A8-04 Zero offset of received data
-100.00 to 100.00
0.00
1
7
1
A8-05 Gain of received data
-10.00 to 10.00
1.00
1
7
1
A8-06 Point-point communication
interruption detection time
0.0s to 10.0s
1.0s
1
7
1
A8-07 Master data sending cycle in
point-point communication
0.001s to 10.000s
0.001s
1
7
1
A8-11 Window width
0.20 to 10.00 Hz
0.50 Hz
1
7
1