5. Quick Setup
- 78 -
5
CONTINUE Para. Parameter name Default Commission
if it is VF control
Set VF parameters F3-00 V/F curve selection 0
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
SETTING RANGE: 0 to 11;
F3-01 Torque boost 0.0
0.0 to 30.0 %;
NOTE: if it is 0, then auto torque boost is activated, and it
is recommended to use auto torque boost.
F3-02 Frequency limit of torque boost 50.00
0.00 Hz to maximum output frequency
F3-03 Multi-point V/F frequency 1 0.00
0.00 Hz to F3-05
F3-04 Multi-point V/F voltage 1 0.0
0.0 to 100.0 V
F3-05 Multi-point V/F frequency 2 0.00
F3-03 to F3-07, Hz
F3-06 Multi-point V/F voltage 2 0.0
0.0 to 100.0 V
F3-07 Multi-point V/F frequency 3 0.00
F3-05 to rated motor frequency F1-04, Hz
F3-08 Multi-point V/F voltage 3 0.0
0.0 to 100.0 V
Trial RUN Use operating panel, or digital input terminal, or serial
communication control, to start inverter, check if the
running performance satises your application. If yes, then
go forward to next step, if NO, then go back to check.