- 78 -
CONTINUE Para. Parameter name Default Commission
if it is VF control
Set VF parameters F3-00 V/F curve selection 0
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
SETTING  RANGE: 0 to 11;
F3-01 Torque boost 0.0
0.0 to 30.0 %; 
NOTE: if it is 0, then auto torque boost is activated, and it 
is recommended to use auto torque boost.
F3-02 Frequency limit of torque boost 50.00
0.00 Hz to maximum output frequency
F3-03 Multi-point V/F frequency 1 0.00
0.00 Hz to F3-05
F3-04 Multi-point V/F voltage 1 0.0
0.0  to 100.0 V
F3-05 Multi-point V/F frequency 2  0.00
F3-03 to F3-07, Hz
F3-06 Multi-point V/F voltage 2 0.0
0.0 to 100.0 V
F3-07 Multi-point V/F frequency 3 0.00
F3-05 to rated motor frequency F1-04, Hz
F3-08 Multi-point V/F voltage 3 0.0
0.0 to 100.0 V
Trial RUN Use operating panel, or digital input terminal, or serial 
communication control, to start inverter, check if the 
running performance satises your application. If yes, then 
go forward to next step, if NO, then go back to check.
CONTINUE Para. Parameter name Default Commission