IPE300 series engineering VFD Function parameter list
-158-
Function
code
Name
Description
Default
Modify
P08.02
ACC time 3
inverter unit is the first group. The factory
default ACC/DEC time of the VFD is the first
group.
Setting range: 0.03600.0s
Model
depended
P08.03
DEC time 3
Model
depended
P08.04
ACC time 4
Model
depended
P08.05
DEC time 4
Model
depended
P08.06
Running
frequency of jog
The function code is used to define the
reference frequency during jogging.
Setting range: 0.00HzP00.03 (Max. output
frequency)
5.00Hz
P08.07
ACC time for
jogging
ACC time for jogging means the time needed
for the VFD to accelerate from 0Hz to the
max. output frequency (P00.03).
DEC time for jogging means the time needed
for the VFD to decelerate from the max.
output frequency (P00.03) to 0Hz.
Setting range: 0.03600.0s
Model
depended
P08.08
DEC time for
jogging
Model
depended
P08.09
Jump frequency
1
When the set frequency is within the range of
jump frequency, the VFD runs at the
boundary of jump frequency.
The VFD can avoid mechanical resonance
points by setting jump frequencies. The VFD
supports the setting of three jump
frequencies. If the jump frequency points are
set to 0, this function is invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00HzP00.03 (Max. output
frequency)
0.00Hz
P08.10
Jump frequency
amplitude 1
0.00Hz
P08.11
Jump frequency
2
0.00Hz
P08.12
Jump frequency
amplitude 2
0.00Hz
P08.13
Jump frequency
3
0.00Hz
P08.14
Jump frequency
amplitude 3
0.00Hz
P08.15
Amplitude of
wobbling
frequency
0.0100.0% (of the set frequency)
0.0%