EasyManuals Logo
Home>INVT>DC Drives>IPE300 Series

INVT IPE300 Series User Manual

INVT IPE300 Series
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
IPE300 series engineering VFD Function parameter list
-159-
Function
code
Name
Description
Default
Modify
P08.16
Amplitude of
sudden jump
frequency
0.0–50.0% (of the amplitude of wobbling
frequency)
0.0%
â—‹
P08.17
Rise time of
wobbling
frequency
0.1–3600.0s
5.0s
â—‹
P08.18
Fall time of
wobbling
frequency
0.1–3600.0s
5.0s
â—‹
P08.19
Switching
frequency of
ACC/DEC time
0.00–P00.03(Max. frequency)
0.00Hz: No switchover
If the running frequency is greater than
P08.19, switch to ACC/DEC time 2.
0.00Hz
â—‹
P08.20
Frequency
threshold of the
start of droop
control
0.00–50.00Hz
2.00Hz
â—‹
P08.21
Reference
frequency of
ACC/DEC time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight-line ACC/DEC only.
0
â—Ž
P08.22
Output torque
calculation
method
0: Based on torque current
1: Based on output power
0
â—‹
P08.23
Number of
decimal points of
frequency
0: Two
1: One
0
â—‹
P08.24
Number of
decimal points of
linear speed
0: No decimal point
1: One
2: Two
3: Three
0
â—‹
P08.25
Set counting
value
P08.26–65535
0
â—‹
P08.26
Designated
counting value
0–P08.25
0
â—‹
P08.27
Set running time
0~65535min
0min
â—‹
P08.28
Auto fault reset
count
Auto fault reset count: When the VFD uses
0
â—‹

Table of Contents