IPE300 series engineering VFD Basic operation guidelines
-42-
Function
code
Name
Description
Default
P02.08 are autotuned; when the present motor is
motor 2, only P12.06, P12.07, and P12.08 are
autotuned.
P00.18
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
3: Lock keypad parameter
4. Reserved
5: Restore to default value (factory test mode)
6: Restore to default value (including motor
parameters)
Note: After the selected operation is performed, the
function code is automatically restored to 0.
Restoring the default values may delete the user
password. Exercise caution when using this function.
0
P02.00
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P02.01
Rated power of AM
1
0.13000.0kW
Model
depended
P02.02
Rated frequency of
AM 1
0.01HzP00.03(Max. output frequency)
50.00Hz
P02.03
Rated speed of AM
1
136000rpm
Model
depended
P02.04
Rated voltage of AM
1
01200V
Model
depended
P02.05
Rated current of AM
1
0.86000.0A
Model
depended
P02.15
Rated power of SM
1
0.13000.0kW
Model
depended
P02.16
Rated frequency of
SM 1
0.01HzP00.03 (Max. output frequency)
50.00Hz
P02.17
Number of pole
pairs of SM 1
150
2
P02.18
Rated voltage of SM
1
01200V
Model
depended
P02.19
Rated current of SM
1
0.86000.0A
Model
depended

Table of Contents