JetMove D203 7.7 Digital Inputs, Logic Power Supply
Jetter AG 71
LIMIT + Positive
limit switch
(input)
Depending on the
parameter setting, this
input is used as a
positive limit switch.
•DC 24 V
7.5 mA max.
Operating point:
< 6 V low,
> 15 V high
NC or NO contact
LIMIT - Negative
limit switch
(input)
Depending on the
parameter setting, this
input is used as a
negative limit switch.
•DC 24 V
7.5 mA max.
Operating point:
< 6 V low,
> 15 V high
NC or NO contact
INPUT Digital input Depending on the
parameter setting, this
input can be used for
quick stop, position
capture or referencing
without stop.
•DC 24 V
7.5 mA max.
Operating point:
< 6 V low,
> 15 V high
0 V Common
ground
Ground
*)
for all
inputs or for braking
circuit
BRK. Supply Voltage
supply for
the motor
brake
The voltage supply for
the motor brake must be
connected to this
terminal.
DC 24 V
(I < 2.0 A)
Digital Inputs, Brake Terminals
Terminals
X72/X82
Signal Description Specification