9 Diagnostics
84 Jetter AG
F 20 Undervoltage
DC link voltage
The DC link
voltage is less
than the minimum
value
Stop with
emergency
stop ramp
Check the voltage of
the power line
Check the parameter
"U
ZK
min. trip"
Acknowledge failure
F 21 Overvoltage DC
link voltage
The DC link
voltage has
exceeded the
maximum value
Stop with
emergency
stop ramp
Check the voltage of
the power line
In generator
operation reduce
braking power
Acknowledge failure
F 22 The drive has
stalled
The drive could
not overcome the
n=0 threshold
within the time
limit specified by
the parameter
"blocking-triping
time"
Immediate
locking of
controller
Eliminate the cause
of stalling
Acknowledge failure
F 23 Tracking error The tracking error
has exceeded the
limit defined in the
parameter
"tracking error
limit" for the time
specified in
"tracking window
time"
Stop with
emergency
stop ramp
Check the drive
mechanism
Check steepness of
acceleration/
deceleration ramps
and amplifier
parameters in
relation to the
parameters "tracking
error limit" and
"tracking window
time"
Acknowledge failure
F27
(combined with
F01)
Internal supply
error
one or more
internal supply
voltages has fallen
below their limit
Immediate
locking of
controller
Note the number of
error
Return the amplifier
for repair
F28 Error in power
charging circuit
The input current
limitation circuit is
defective.
Immediate
locking of
controller
Check the voltage of
the power line
Note the number of
error
Return the amplifier
for repair
F29 Mains power too
high
The average
mains power is too
high
Immediate
locking of
controller
Acknowledge failure
Reduce the average
load of the motor
Fault Message Table for the JetMove D203
Error Number Type of Error Description Response to
Errors
Troubleshooting