EasyManua.ls Logo

Jetter JetMove D203 - Page 83

Jetter JetMove D203
142 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JetMove D203 9.1 Error Messages
Jetter AG 83
F 13 (combined
with F00)
Internal
checksum error
An internal
checksum error
has occurred
Immediate
locking of
controller
Switch the 24 V
supply off and on
again
If the error occurs
repeatedly, return
the amplifier for
repair
F 14 (combined
with F 00)
Internal
communication
error
An internal
communication
error has occurred
Immediate
locking of
controller
Switch the 24 V
supply off and on
again
If the error occurs
repeatedly, return
the amplifier for
repair
F 15 The hardware
enable is
missing
The software
enable is given
without a
hardware enable
Immediate
locking of
controller
Disable the drive by
means of the
software
Acknowledge failure
F16 Power input
over current
The current at the
power input was to
high
Immediate
locking of
controller
Check input voltage
Reduce mechanical
power of the motor
Acknowledge failure
F 17 Trip of software
limit switch
Actual position is
outside the range
of software limits
and software limit
switches are
active
Stop with
max. current
(torque)
Check destination
position
Acknowledge failure
Run axis back inside
the range of software
limits (software limit
switches will be
active automatically
by entering this
range)
F 18 Trip of hardware
limit switch
One hardware
limit switch was
activated
Stop with
max. current
(torque)
Check destination
position
Check reference
position
Acknowledge failure
Run axis back inside
the range of
hardware limits
(software limit
switches will be
active automatically
at leaving the switch)
Fault Message Table for the JetMove D203
Error Number Type of Error Description Response to
Errors
Troubleshooting

Table of Contents

Related product manuals