TABLE 12 - WEISHAUPT BURNER OIL PUMP CAPACITIES
BURNER
TYPE
BURNER CAPACITY
ON NO. 2 OIL
TYPE OF OIL
PUMP
PUMP CAPACITY
MAXIMUM SUPPLY
PRESSURE
MAXIMUM
OPERATING
TEMPERATURE
GL3 up to 16.5 GPH UNI 2.10 L7 44 GPH (140 kg/h) 30 psi (2.0 bar) 160°F (70°C)
RGL3 up to 16.5 GPH UNI 2.10 L8 66 GPH (210 kg/h) 30 psi (2.0 bar) 160°F (70°C)
GL5 up to 24.5 GPH J6 72 GPH (230 kg/h) 30 psi (2.0 bar) 160°F (70°C)
RGL5 up to 24.5 GPH E7 97 GPH (310 kg/h) 70 psi (5.0 bar) 190°F (90°C)
GL7 up to 40.0 GPH J6 72 GPH (230 kg/h) 30 psi (2.0 bar) 160°F (70°C)
GL7 up to 46.0 GPH J7 116 GPH (370 kg/h) 30 psi (2.0 bar) 160°F (70°C)
RGL7 up to 46.0 GPH TA2 165 GPH (525 kg/h) 70 psi (5.0 bar) 190°F (90°C)
GL8 up to 60.0 GPH J7 116 GPH (370 kg/h) 30 psi (2.0 bar) 160°F (70°C)
RGL8 up to 60.0 GPH TA3 247 GPH (785 kg/h) 70 psi (5.0 bar) 190°F (90°C)
GL9 up to 68.0 GPH J7 116 GPH (370 kg/h) 30 psi (2.0 bar) 160°F (70°C)
GL9 up to 91.0 GPH TA2 165 GPH (525 kg/h) 70 psi (5.0 bar) 190°F (90°C)
RGL9 up to 91.0 GPH TA3 247 GPH (785 kg/h) 70 psi (5.0 bar) 190°F (90°C)
RGL10 up to 103.0 GPH TA3 247 GPH (785 kg/h) 70 psi (5.0 bar) 190°F (90°C)
RGL11 up to 133.0 GPH TA4 330 GPH (1050 kg/h) 70 psi (5.0 bar) 190°F (90°C)