4 Configuration parameters
H
Systematic errors, such as those caused by an unsuitable probe mount-
ing, for example, can be compensated using fine calibration.
Example:
A probe covers a temperature range from 200 to 300°C. It has been fitted
in a tunnel oven so unfavorably as to always indicate 10°C less than the
temperature of the charge. The incorrect measurement can be corrected
through fine calibration.
Actual start value : 200°C
Set start value : 210°C
Actual end value : 300°C
Set end value : 310°C