4 Configuration parameters
52
4.2.3 Configuration - Analog inputs
Enable options
Enabling code
Configuration
➔ Instrument data
➔ Enable options
➔ Enabling code
Enter enabling code Enter the enabling code
you have received here.
Parameter Value/selection Description
Sensor Configuration
➔ Analog inputs
➔ Analog input 1—6
➔ Sensor
Off,
Res. therm.,
Thermocouple,
Current,
Voltage,
Math
Depending on the select-
ed sensor, only the relevant
parameters can be
selected for configuring the
analog input.
Linearization Configuration
➔Analog inputs
➔ Analog input 1—6
➔ Linearization
Linear, Pt100, Pt100 JIS,
Ni100, Pt500, Pt1000,
Pt50, Cu50, Fe-Con J,
NiCrCon E, Ni-CrNi K,
NiCrSi N, Cu-Con T,
PtRhPtRh B,
PtRh-Pt R, PtRh-Pt S,
Cu-Con U, Fe-Con L,
W3W25Re, W5W26Re
Connection circuit Configuration
➔Analog inputs
➔ Analog input 1—6
➔ Connection circuit
2—4 wire
Cold junction Configuration
➔Analog inputs
➔ Analog input 1—6
➔ Cold junction
Internal Pt100,
External const
External CJ
temperature
Configuration
➔ Analog inputs
➔ Analog input 1—6
➔ Ext. CJ temp.
-50 to +150°C External cold junction tem-
perature for thermocouples
Range start Configuration
➔Analog inputs
➔ Analog input 1—6
➔ Range start
any value
0mA
Range end Configuration
➔Analog inputs
➔ Analog input 1—6
➔ Range end
any value
20mA
Start temperature Configuration
➔ Analog inputs
➔ Analog input 1—6
➔ Start
temperature
any value Only for sensor types:
current, voltage with linear-
ization for resistance ther-
mometer, thermocouple.
Only for signals which are
not yet linearized.