EasyManua.ls Logo

Juniper SRX4100 - Figure 11: Airflow through the Chassis; Table; Table 17: Clearance Requirements for the SRX4100 Services Gateway

Juniper SRX4100
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 11: Airflow Through the Chassis
If you are mounting the services gateway on a rack or cabinet along with other
equipment, ensure that the exhaust from other equipment does not blow into the
intake vents of the chassis.
For service personnel to remove and install hardware components, there must be
adequate space at the front and back of the services gateway as indicated in
Table 17 on page 26.
Table 17 on page 26 provides information about the clearance requirements for
maintaining optimum airflow and the distancesnecessary to facilitate easy maintenance
of the services gateway.
Table 17: Clearance Requirements for the SRX4100 Services Gateway
Requirement for Clearance
Recommended
ClearanceLocation
Space for service personnel to remove
and install hardware components
34.25 in. (87 cm)Front of the chassis
Space for service personnel to remove
and install hardware components
17.4 in. (44.2 cm)Rear of the chassis
Space for cable management and
organization
2.5 in. (6.35 cm)Between front-mounting flange
and rack or cabinet edge
Space for the cooling system to
function properly and to maintain
unrestricted airflow around the chassis
6.0 in. (15.24 cm)Between both sides of the
chassis and any
non-heat-producing surface
such as a wall or cabinet side
Copyright © 2017, Juniper Networks, Inc.26
SRX4100 Services Gateway Hardware Guide

Table of Contents

Other manuals for Juniper SRX4100

Related product manuals