3.5 >EE< Configuration of MULTITARIFF
MULTICAL
®
Example: EE=11 (Power tariff)
402 has 2 extra registers, TA2 and TA3, which can accumulate energy E1 or E3 (E=20 accumulates
volume) parallel with the main register based on the limits programmed into tariff limits TL2 and TL3.
TA2 shows energy consumed…
…above the power limit TL2
EE= TARIFF TYPE FUNCTION
Country code 2xx
Country code 3xx
Country code 5xx
Country code 6xx
Country code 7xx
Country code 8xx
Country code 9xx
00 No active tariff
No function
11
Power tariff
Energy is accumulated in TA2 and TA3 on the basis of the power
limits entered in TL2 and TL3
• • •
12
Flow tariff
Energy is accumulated in TA2 and TA3 on the basis of the flow
limits entered in TL2 and TL3
• • •
13
Cooling tariff
Energy is accumulated in TA2 and TA3 on the basis of the ∆t limits
entered in TL2 and TL3
• • •
14
Flow temperature tariff
Energy is accumulated in TA2 and TA3 on the basis of the tF limits
entered in TL2 and TL3
• • •
15
Return temperature tariff
Energy is accumulated in TA2 and TA3 on the basis of the tR limits
entered in TL2 and TL3
• • •
19
Time controlled tariff
TL2=Start time for TA2
TL3=Start time for TA3
• • •
20
Heat/cooling volume tariff
(TL2 and TL3 are not used)
Volume (V1) is divided into TA2 for heat (T1>T2) and TA3 for
cooling (T1<T2). (Recommended for heat/cooling applications)
• • •
21
PQ-tariff
If P>TL2 energy is saved in TA2 and if Q>TL3 energy is saved in TA3 •
•
•
See paragraph 7.9 for further details on the tariff registers.