MULTICAL® 402
50
Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016
7.8.3 Info event counter
Info event counter
Enumeration each time the info code is changed
(the info code is added to the info-event counter and
data logged when it has existed for an hour).
The info event counter of a new meter will be 0 as
“transport mode” prevents counting during
transportation.
Info code ”info” in display
Registration in info, daily,
monthly or yearly logger
Enumeration of Info event
00001
No Yes
With each ”Power-On-Reset”
00004, 00008
Yes Yes
When Info 4 or 8 is set or removed.
Max. 1 per temperature measurement
4096, 16384
Yes Yes
When Info is set and when Info is deleted.
Max. one per code, per 24 hrs.
7.8.4 Transport mode
When the meter leaves the factory it is in transport mode, i.e. the info codes are active in the display only, not in
the data logger. This prevents ”infoevent” from counting during transportation and irrelevant data from being
saved in the info logger. The first time the meter accumulates the volume register after the installation, the info
code automatically becomes active.