ACD320 user manual Parameter Description
- 96-
F6.02 Data pattern
0: No check(N,8,1)for RTU
1: Odd check(E,8,1)for RTU
2: Evencheck(O,8,1)for RTU
4: Odd check(E,8,2)for RTU
5: Evencheck(O,8,2)for RTU
6: No check(N,7,1)forASCII
7: Odd check(E,7,1)for ASCII
8: Evencheck(O,7,1)forASCII
9: No check(N,7,2)forASCII
10: Odd check(E,7,2)for ASCII
11: Evencheck(O,7,2)forASCII
12: No check(N,8,1)forASCII
13: Odd check(E,8,1)for ASCII
14: Evencheck(O,8,1)forASCII
15 : No check(N,8,2)forASCII
16: Odd check(E,8,2)for ASCII
17: Evencheck(O,8,2)forASCII
0
The data pattern set by inverter must be the same as data pattern set bymaster
machine.Otherwise,communication can not accomplish.
11-bits(for RTU)
DATA Frame:8-N-2
DATA Frame:8-E-1
DATA Frame:8-O-1