ACD320 user manual Parameter Description
- 71-
command channel.
12
Multi-speed terminal
1
8 stages speed can be set up via these 3 terminals digital state
combination.
Note:multi-speed 1 is the low position, and multi-speed 3 is the
high position.
13
Multi-speed terminal
2
14
Multi-speed terminal
3
15
ACCE/DCCE time
selection terminal
2 kinds ofACCE/DCCE time can be chosen via these two terminals
digital state combination.
Terminal
ACC/DCC time
selection
Parameter
O F F ACCE time 0 F0.08F0.09
N
ACCE time 1 F4.00F4.01
16 PID control pause
PID is temporarily out of work, and the inverter keeps its current
frequency output
17 Traverse pause
The inverter pauses at its current output frequency.After this
function is cancelled, continue to start its traverse operation at its
current frequency.
18 Traverse reset The inverter is back to its center frequency output.
19
Acceleration/
Deceleration forbid
Ensure the inverter is not interfered by external signals ( excluding
stop command ), maintaining its current output frequency.
20
External sleep signal
Please refer to F7.28 for detailed description.
23
One driving two
circularly water
supply mode is
ineffective
One driving two circularly water supply mode is ineffective, and it
is used in the case of manual operation.
21,2224 Reserved
25
Simple PLC run reset To restore the PLC run to initial state.
26
Simple PLC run
ineffective
PLC run pause.
27
Switch to the set of
ACI frequency.
No matter which value F0.03 is set, frequency setting channel is
ACI effective when terminal is closed, and F0.03 run command
channel recover after terminal isopened.
28 Jog key Jog run according to current status(forward or reverse)
29
Torque control
forbidden
The inverter switch the control mode from torque control to speed
comtrol.
30 Frequency When terminal is closed, the frequency value UP/DOWN has set is