Continued: Error messages
E25 No measuring current (for low load operation, the stag-
es are switched o after one hour)
Alarm relay
E26 Capacitor current too high (with induced current mea-
surement)
Alarm relay
E27 Check fuse (for induced current measurement, no cur-
rent increase due to connection of a stage)
Alarm relay
E28 Loss of capacitance Alarm relay
E29 Contactor defect
(current does not decrease when stage is switched o)
Alarm relay
E30 Stage locked due to induced current error Alarm relay
E31 Induced current limit violated
E33 Relay module 1 cannot be reached Alarm relay
E34 Relay module 2 cannot be reached Alarm relay
E35 Relay module 3 cannot be reached Alarm relay
E36 Relay module 4 cannot be reached Alarm relay
E37 Relay module 5 cannot be reached Alarm relay
E38 Temperature module 1 cannot be reached Alarm relay
E39 Temperature module 2 cannot be reached Alarm relay
E40 Temperature module 3 cannot be reached Alarm relay
E41 Temperature module 4 cannot be reached Alarm relay
E42 Temperature module 5 cannot be reached Alarm relay
E43 Induced current module 1 cannot be reached Alarm relay
E44 Induced current module 2 cannot be reached Alarm relay
E45 Induced current module 3 cannot be reached Alarm relay
E46 Induced current module 4 cannot be reached Alarm relay
E47 Induced current module 5 cannot be reached Alarm relay
E48 Induced current module 6 cannot be reached Alarm relay