V7.00
24905_EDEBDA0272-5019-1_EN
40
Display as example:
Main menu: = cosφ actual (instantaneous)
Stage mode: = Stage 1 Manual switching On
Stages 2 to 12 Automatic mode On
Stages 13 to 16 Automatic mode O
Fan: = On
Alarm relay: = On
Alarm message:
= exists ()
Menu description: = cosφ actual (instantaneous)
Measured cosφ: = 0.87 inductive
Switching on/o: = Switch on,
since capacitor power is missing
Missing
compensation power
= 57.0 kvar
Additional modules
= exists ()
By pressing the button
, you can display the maximum value of the missing com-
pensation power.
The value is displayed in kvar, with time and date stamp. The value is only displayed if all
available stages are switched on and the congured alarm CosPhi is not reached when
the set alarm delay time has elapsed.
The respective value is a maximum value (maximum indicator function) accumulated
during the alarm delay time.
As soon as the value is entered,
the status message E12 “facility too small” is displayed in the Messages submenu with a
time stamp and kvar specication.
NOTE
The value displayed here is an average value of the set alarm delay time. I.e. this value
and the maximum value of the missing compensation power can be dierent.
System operation