EasyManua.ls Logo

KBR multicomp D6 7 Series - Page 68

KBR multicomp D6 7 Series
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V7.00
24905_EDEBDA0272-5019-1_EN
68
System operationSystem operation
Q-Control examples:
Mode DI 3 Q/P
rated
(change by digital input):
When DI 3 Q (change by digital input) is set, there are 4 available values (A, B, C and D),
which can be activated through the digital input module multisio D2-4DI. If an input
from this module is selected, the corresponding Q/Pn mode will be active after the set
delay time t-delay (0–250 seconds) has elapsed. The Q/Pn2 mode (power recovery) has no
function here.
Example settings:
Mode DI 3 Q
t-delay 000 seconds
Q/Pn A 0.50 ind.
Q/Pn B 0.33 ind.
Q/Pn C 0.33 cap.
Q/Pn D 0.50 cap.
NOTE
If no input from the DI module is selected, then Q/Pn is 0.000.
Mode AI 3 Q/P rated (change by analog input):
When AI 3 Q (change by analog input) is set, the Q/Pn value can be preset through an
analog input. Conguration is performed through 2 control points (A and B). At the AI
module, the channel can be set to voltage input (0–10V) or current input (0–20mA)
with DIL switches. The range adaption is made using the parameter AI 4-20. When AI
4-20 NO” is set, the range is 0–20mA or 0–10V. The Q/Pn2 value (power recovery) has no
function in this mode.
Only the rst channel of the AI module is used.
If the input from this module is connected accordingly, the corresponding Q/Pn value
will change in the range from A to B after the set delay time t-delay (0–250 seconds) has
elapsed.

Table of Contents

Related product manuals