Under the item Auto conguration mode, you can start automatic monitoring of the
connected capacitor stages under the menu item
Extra , Commissioning , Stages , Auto conguration mode , Start.
First, the congured parameters are displayed.
If needed, these can be corrected here or, if they are already correct, conrmed with
N
(OK). After the last conrmation, all capacitor stages are switched o, and the auto
conguration mode can be started. During the procedure, the stages are switched on
individually, and the stage power is determined. This can be interrupted by pressing
(Stop) at any time. The progress is illustrated in the status display. Along with this,
the connected capacitor stages are hooked up, one after the other. From the current
consumption measured, the multicomp D6-xxx-7 determines the corresponding stage
power. After successfully determining the stage power, the result is displayed and can be
saved by conrming it (press button
(Return) repeatedly, until the prompt Save
parameters Yes/No appears). If measurement errors have occurred, they can be discard-
ed, and the mode be restarted.
A prerequisite for performing the auto conguration mode is, however:
1. Measurement via induced current transformer and current measuring module multisio
D2/4CI or energy measuring module multimess D4
2. Correct programming of the primary and secondary voltage
3. Correct programming of the primary and secondary current of the induced current
transformer
4. Correct programming of the primary and secondary voltage of the energy measuring
module
5. Possible additionally connected modules must be detected and stored with the help of
the Settings , Module / Display , Module management menu item
6. The capacitive or inductive stages must be connected
If all these prerequisites are met, the auto conguration mode of the stage powers can be
started.
Under the item Stage parameters direct input, all stage parameters can also be entered
manually.
The following parameters are available:
1. Stage power from 0.00 to 999.9 kvar
2. Capacitive or inductive stages
System operationSystem operation