US - Basic Setup Parameters
Absolute Analog Speed
A uni-polar 0...+10VDC analog signal connected to terminals AN1+ and AN1-
controls the speed from 0...High Speed. The High Speed must be set in
LS02. For controllers which do not output 10V corresponding to High Speed,
the analog input can be scaled by LA05 AnIn1 Gain. In addition, the AN1+
and AN1- inputs can be programmed to receive the speed prole as either a
voltage or current signal using parameter LA50.
The speed prole acceleration, deceleration and jerk rates are externally
generated by the controller. It is possible to limit external prole rates by
setting LS15 = Internal Prole (4) and adjusting the according LS20-25 High
Speed prole rates.
The direction is determined by digital inputs assigned in LI04-11 as Up (25)
and Down (26). Both direction signals cannot be signaled simultaneously at
the beginning of a run, otherwise ‘Direction Selection Failure will occur.
Bi-polar Analog Speed
A bi-polar, 0... ±10V analog signal connected to the terminals AN1+ and AN1-
controls the speed from 0...±High Speed. The High Speed must be set in
LS02. For controllers which do not output 10V corresponding to High Speed,
the analog input can be scaled by LA05 AnIn1 Gain. In addition, the AN1+
and AN1- inputs can be programmed to receive the speed prole as either a
voltage or current signal using parameter LA50.
The speed prole acceleration, deceleration and jerk rates are externally
generated by the controller. It is possible to limit external prole rates by
setting LS15 = Internal Prole (4) and adjusting the according LS20-25 High
Speed prole rates.
The direction is determined by the polarity of the analog signal, although a
direction input is needed to control the start and stop routines. A digital input
must be assigned in LI04-11 as Up (25) or Down (26). Either or both Up and
Down inputs can be assigned but the direction selected does not matter since
the actual direction is determined by polarity of the analog signal. If both
directions are assigned as inputs, they cannot be signaled simultaneously at
the beginning of a run, otherwise ‘Direction Selection Failure will occur.

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals