241
FB - Field Bus Parameters
FB10-12: Serial Communication Setup
Node ID must be set to agree with Node ID used in serial communication
service structure (default = 1).
The serial communication baud rate corresponding to port X6C.
As a note, the LX12 Baud Rate corresponds to the (Combivis) diagnostics
port X6D.
Watchdog of serial communication between the LCD keypad operator serial
communications port, X6C, and controller.
Active only when Mode = Run (Home or Diagnostics Screen #6).
As a note, the LX09 Serial Comm. Watchdog Time corresponds to the
communication between the LCD keypad operator and the inverter control card.
FB10
DIN66019 Field Bus
Node ID
FB11
DIN66019 Field Bus
Baud Rate
FB12
DIN66019 Field Bus
Watchdog