Operation Manual ServoOne Supply Unit
18
ID no.: 1101.21B.6-00 Date:04/2020
ServoOne DC BG1
ServoOne DC BG2
ServoOne DC BG3
ServoOne DC BG4
ServoOne
Supply unit BG5
B
A
Figure 3.4 Butt mounting axis group, wall mounting with supply unit BG5
ServoOne DC BG1
ServoOne DC BG2
ServoOne DC BG3
ServoOne DC BG4
ServoOne DC BG5
ServoOne DC BG6a
wall mounting
ServoOne
Supply unit BG6a
wall mounting
B
A
Figure 3.5 Butt mounting axis group, wall mounting with supply unit BG6a
3.3 Mounting supply unit,
wall mounting housing variant
1.
Arrange the devices starting from the supply unit to the right or left sorted in
descending order by power rating to minimise thermal interaction. Pay attention
to the notes on effective EMC installation prior to mounting the devices and
components in the switch cabinet.
• Align the supply unit BG5 and all ServoOne DC axis controllers in a line along the
top edge of the devices (see line A in Figure 3.4).This action is necessary to be
able to make the DC link connections.
• Align the supply unit BG6a and all ServoOne DC axis controllers in a line along
the top edge of the devices (see line A in Figure 3.5). This action is necessary to
be able to make the DC link connections. Move down the mounting bores for
the supply unit BG6a and the ServoOne DC BG6a by approx. 20 mm
(see red line B in Figure 3.5). It is imperative you pay attention to the information
in Table 3.1 on the mounting distances.
2.
Mark out the position of the tapped holes on the backing plate.
Cut a thread for each xing screw in the backing plate.
Note the mounting distances. Also pay attention to the bending radius of the
connection cables. For dimensional drawings/hole spacing see Figure 3.6 and
Table 3.1.
3.
Mount the supply unit vertically and butt-mounted in a row on the backing plate.
The contact area must be bare metal.
Mechanical installation