Operation Manual ServoOne Supply Unit
80
ID no.: 1101.21B.6-00 Date:04/2020
NOTE:
Do not use material combinations with contact corrosion in the cooling circuit,
such as aluminium and copper. This can lead to leaks and blockages of the
cooling lines.
Size BG5 BG6a BG7
Device
SO84.040
SO84.076
SO84.115
SO84.170
SO84.375
SO84.540
Coolantpressure
(ratedvalue/
maximumvalue)
1bar/
2bar
Coolant ow rate
1)
(rated valueapprox. /
maximum value approx.)
8lpermin/
11lpermin
11lpermin/
13lpermin
12lpermin/
14lpermin
1) For devices without internal braking resistor
Table A.13 Hydrological data for the liquid cooling
NOTE:
The requirements on liquid-cooled devices as per DIN EN 61800-5-1 are to be
ensured by the user. On this issue pay attention in particular to the require-
ments in chapter 3.5 / 4.2.2 / 4.2.3 / 4.5
A.4 Hydrological data for the liquid cooling
CAUTION! Damage to the device due to condensation on the cooling plate
• Carelessness can cause condensation on the cooling plate and as a
consequence irreparable damage to the device!
Thetemperatureofthecoolingplateisnotallowedtobemorethan10°Cbelowtheambi-
enttemperature.
NOTE:
Adequate heating of the water chiller is to be provided by the customer.
Requirements Limits
Coolantquality
Recommended:tapwater+corrosioninhibitor
Corrosionprotectionthrough:10-20%volEthyleneglycol
Limit concentrations:
Calcium <50ppm
Magnesium <50ppm
Totalalkalineearthions <100ppm
Chlorides <25ppm
Sulphates <25ppm
Soiling
Thecoolantmustbeaspureaspossibletoensurethechannelsarenotclogged.With
asuspendedmatterconcentrationofmorethan15mg/dm³,continuouspurication
isrecommended.
Coolanttemperature
Thecoolanttemperaturecanbebetween5°Cand40°C.However,thecoolant
temperaturemustnotbemorethan10°Kbelowtheambienttemperaturetoprevent
condensationontheheatsink.
Coolerandcoolerconnec-
tionmaterial
Aluminium
Table A.12 Requirements, liquid cooling
Appendix