Operation Manual ServoOne Supply Unit
42
ID no.: 1101.21B.6-00 Date:04/2020
ServoOne DC BG 1
ServoOne DC BG 2
ServoOne DC BG 3
ServoOne DC BG 4
ServoOne DC BG 5
PE
PE
X11
PE
X11
PE
X11
PE
X11
PE
X11
PE
X11
ServoOne DC BG6a
with liquid cooling
ServoOne
Supply unit BG7
with liquid cooling
Figure 4.16 Schematic: connection of the protective earth conductor with supply unit BG7
4.5.4 Protective earth conductor connection other components
1.
Connect the PE connections on all other components, such as mains lters, chokes
etc. in a star topology to the PE rail (main earth) in the switch cabinet. During this
process also take into account the instructions in chap.4.5
DANGER! Risk of injury due to electrical power!
• Carelessness will result in serious injuries or death.
Nevermakeordisconnectelectricalconnectionswhiletheyareelectricallylive!Beforemaking
anychange
thedeviceistobedisconnectedfromthemains.Dangerouslyhighvoltages≥50Vcanbe
presentontheDClinkconnectionsandothercomponentsinthemainsinputareaafterpower
off.Socheckthatelectricalpowerisnotpresent!Seechap.4.1
Figure 4.15 Detail: connection of the protective earth conductor
4.5.3 Protective earth conductor (X11)supply unit BG7
1.
Earth the supply unit and each DC axis controller BG7 and BG6a separately!
Connect the PE connection X11/PE on the supply unit to the PE rail (main earth) in
the switch cabinet.
Select the protective earth conductor cross-section according to chap.4.5.
2.
Earth all other DC axis controllers BG5 to BG1 via a common protective earth
conductor! Connect in series all other PE connections X11/PE on the butt-mounted
DC axis controllers.
Connect the PE connection X11/PE on the rst DC axis controller in a row to the PE
rail (main earth) in the switch cabinet.
For this purpose use the pre-assembled protective earth conductors.
Electrical installation