4.7 Connection of the supply voltages
The supply of power to the ServoOne is separate for the control section and power
section. The control supply is always to be connected rst in the sequence so that the
operation of the ServoOne can be checked rst and the device parameters congured
for the planned application.
DANGER! Risk of injury due to electrical power!
• Carelessness will result in serious injuries or death.
Dangerousvoltagemaybepresentatthedevice,evenifthedeviceisnotemitting
anyvisualoraudiblesignals/indications(e.g.withmainsvoltageappliedtoterminalX12and
nocontrolsupply+24VDConX9/X10)!
Priortoworkingonthedevice,checkthereisnosupplyofelectricalpowerpresent.
Seechap.4.1
4.7.1 Control supply 24VDC (X9, X10) for BG5 and BG6a
+ −+ − +− + +− +
24 V DC
max. 10 A
+ −
L1 L2
L3 N +− +
HREL
X21 X9/10
X9/10X9/10
X11
X11X11
Figure 4.19 Connection for control supply
NOTE:
By means of suitable measures provide adequate cable protection (e.g.
fuse 10AgG). If the permissible current carrying capacity is exceeded, an
additional separate control supply must be connected.
NOTE:
Along with the control section, the external control supply also supplies the
digital inputs and outputs (I
CONTROL SECTION
+ I
I/O
). Also pay attention to the current
24V DC
GND
PE GNDµP
DGND
complex, in part
non-lineare
impedance
RC ethernet Polyswitch
GNDµP
GNDµP
GNDµP
X4/15
ISD00
ISD01
I
LIM
X4/21
ISD06
X4/10
ENPO
I
LIM
X4/22
ISDSH
I
LIM
X4/7
OSD00
X4/3
ISA00+
KTY sensor for step-up mains choke
X4/4
ISA00-
ISD02
ISD03
ISD04
ISD05
A/D
A/D
ISA01+
X4/5
X4/6
ISA01-
X4/14
GNDµP
GNDµP
GNDµP
DGND
DGND
DGND
DGND
DGND
DGND
DGND
DGND
X4/2
ϑ
F1
ϑ
F2
X4/13
DGND
X4/1
ϑ
F3
ϑ
F3
GNDµP
GNDµP
GNDµP
ϑ
F4
V
µP
V
µP
µP
X4/8
OSD01
X4/9
OSD02
X5/ϑ +
X5/ϑ −
RSH
X4/12
X4/11
OSD04
X4/23
X4/24
USB1.1
X2
Ethernet
X3
GNDµP
V
µP
PE
X44/1
X44/2
U
H
Supply
control electronic
24 V DC
GNDµP
X44/3
X44/4
U
V
internal relay,
electrical isolation
Mains synchronization
X45
L1
L2
L3
N
Figure 4.18 Electrical isolation concept, BG7
Electrical installation

Table of Contents

Other manuals for Keba ServoOne Series

Related product manuals