Appendix E: Releasing Module
P/N 3102351-EN • REV 005 • ISS 28DEC18 249
Don’t configure Disable members using the User key for correlation groups with panel
events.
Install a relay confirmation circuit to indicate when the release and prerelease circuits are
active.
Don’t power the REL from the panel. You must power the REL using a compatible power
supply. See the GSA-REL Technical Reference Manual (P/N 387515-EN) for a list of
compatible power supplies.
REL fault messages
Table 55 below lists the messages you may see for the REL on the panel’s LCD.
Table 55: REL fault messages
Device
Condition LED LCD message
Monitor (Abort)
Short Monitor Monitor
Open Trouble Trouble
Abort [1]
Expanded message: Monitor Open
Pull (Manual)
Short Alarm Pull station
Manual [1]
Expanded message: Pull station
Open Trouble Trouble
Manual [1]
Expanded message: Pull station open
Supervised
Output
(Prerelease_1)
Short Trouble Trouble
Prerelease_1 [1]
Expanded message: Supervised output short
Open Trouble Trouble
Prerelease_1 [1]
Expanded message: Supervised output open
None
(Prerelease_2)
Short Trouble Trouble
Prerelease_2 [1]
Expanded message: Supervised output short
Open Trouble Trouble
Prerelease_2 [1]
Expanded message: Supervised output open

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217