Chapter 2: Front panel programming
50 P/N 3102351-EN • REV 005 • ISS 28DEC18
Description
For duct smoke detectors. All activations are immediately considered as alarms.
The panel and detector cannot be reset to normal until the smoke condition has
cleared. [1]
Duct supervisory (latching and
nonlatching)
Duct supervisory latching.
Detectors with this device type when activated immediately places the panel in
the supervisory state, turns on supervisory LEDs, and activates the supervisory
relays. The detectors remain active until the smoke condition clears and the
panel is reset.
Duct supervisory nonlatching.
Detectors with this device type when activated immediately places the panel in
the supervisory state, turns on supervisory LEDs, and activates the supervisory
relays. The detectors remain active until the smoke condition clears. Resetting
the panel is not required.
)
For heat detectors. All activations are immediately considered as alarms.
Detectors cannot be restored until the condition causing the activation clears and
the panel is reset. [1]
For heat detectors with rate-of-rise. All activations are immediately considered as
alarms. Detectors cannot be restored until the condition causing the activation
clears and the panel is reset. [1]
For smoke detectors and contact devices. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored to
normal and the panel is reset. [1]
For smoke detectors and contact devices. Two-wire smoke detector activations
are verified (delayed and confirmed) before activating an alarm. Four-
detectors and contact devices are not verified and immediately considered as
alarms. Circuit cannot be restored until devices are restored to normal and the
panel is
reset. [1]
For detectors that trigger an active (supervisory) event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
For detectors that trigger an active (supervisory) event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is not required.
Heat and CO detectors (HC
D)
For heat + CO detectors that trigger an active alarm event (fixed-temperature
heat or CO).
The panel and detector cannot be restored until devices are restored to normal
and the panel is reset. [1]