Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 51
Description
Heat + CO monitor latching
For heat + CO detectors that trigger an active alarm event (fixed-temperature
heat) or a CO latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Heat + CO monitor
nonlatching
For heat + CO detectors that trigger an active alarm event (fixed-temperature
heat) or a CO nonlatching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the heat type
event. Resetting the control panel is not required for CO monitor nonlatching. [1]
O supervisory
For heat + CO detectors that trigger an active alarm event (fixed-temperature
heat) or a CO latching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Heat + CO supervisory
nonlatching
For heat + CO detectors that trigger an active alarm event (fixed-temperature
heat) or a CO nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the heat type
event. Resetting the panel is not required for CO supervisory nonlatching. [1]
For heat with rate of rise + CO detectors that trigger an active alarm event (rate-
of-rise heat or CO).
The panel and detector cannot be restored until devices are restored to normal
and the panel is reset. [1]
Heat ROR + CO monitor
latching
For heat with rate of rise + CO detectors that trigger an active alarm event (rate-
of-rise heat) or a CO latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Heat ROR + CO monitor
nonlatching
For heat with rate of rise + CO detectors that trigger an active alarm event (rate-
of-rise heat) or a CO monitor nonlatching.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the heat type
event. Resetting the control panel is not required for CO monitor nonlatching. [1]
Heat ROR + CO supervisory
latching
For heat with rate of rise + CO detectors that trigger an active alarm event (rate-
of-rise heat) or a CO supervisory latching event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Heat ROR + CO supervisory
nonlatching
For heat with rate of rise + CO detectors that trigger an active alarm event (rate-
of-rise heat) or a CO nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the heat type
event. Resetting the control panel is not required for CO supervisory nonlatching.
[1]