KW Aufzugstechnik GmbH OPERATING MANUAL DAVID-613
DAVID-D613-V125-E 13.04.2021 Page - 234 -
1.) Move the limit switch position UP (100mm
above flushing) with the backflow regulator. Eleva-
tor car stops, when reaching the position.
2.) Enter yes in the menu.
The ANTSsafe limit switch UP position is automati-
cally saved!
Reach top level landing position (1400 mm under
flush) with the return control and enter YES in the
menu.
Move limit switch position UP ( 100mm over flush)
with the return control. Elevator car stops on
reaching the position.
The ANTSsafe limit switch UP position is automati-
cally saved!
3.5 Learning the lower limit switch
1.)Enter YES in the menu.
2.) Move the limit switch position DOWN (100mm
over flush) with the return control. Elevator stops
on reaching the positon.
The ANTSsafe limit switch DOWN position is auto-
matically saved!
Note: From now on the SiKr is closed, if
the elevator is not in the limit switch!
3.6 Entry Distance – Lower Delay Control Point
Enter and change the value, OFF, 2 to 500 cm;
Can be changed later -. possible in inspection
mode or return to safe state
Vnenn: 1,6 m/s -> 300 cm
Vnenn: 2,0 m/s -> 350 cm
ANTSsafe Delay control down was stored.
3.7 Entry Distance – Upper delay control point