7.4 Basic setup
In this section the settings required for using the device as prescribed are summarized. For more exten-
sive settings refer to the appendix.
7.4.1 Setting the overtemperature switch-off point T
max
Warning !
Overheating due to entering an incorrect T
max
and set-
point temperature
Burns, scalds, fire
• Set T
max
in each case according to the heat transfer
liquid used (at least 25 K below fire point).
Hold the key
pressed during the complete setting procedure:
− Press the enter key
.
The entry window appears. The cursor flashes under the T
max
value. The maximum and minimum adjustable temperature
values are displayed.
− Change the value with
or .
Note: With a longer depression the figures increment faster.
− Single figures can be selected by pressing
or .
− Confirm your choice with the enter key
.
On releasing
you are returned to the menu level without any change.
For T
max
the following applies: 5 K above desired bath temperature, but at least 25 K below the fire point
of the heat transfer liquid used.
- - -
סּ OK
- - -
Tmax
Max. temperature
Max: 205
Min: 0
85