25/08/2011/ YACE0088 Appendix with settings 99
Access to the main menu level is obtained by pressing the
enter key
.
Selection and confirmation of Æ Setup Æ Control Æ
Contr.parameter Æ intern Pt100.
The adjacent menu window appears. Apart from the control
parameters the currently set values are displayed.
Under the menu point "Tv manual/auto" you can select
between manual and automatic entry using
.
The selection "automatic" is displayed in the menu line by (au-
to). If "automatic" is selected, the entry is blocked for the pa-
rameters Tv and Td.
Select and confirm parameters with
or and .
The appropriate edit window appears with Min and Max figures
for the parameter values Xp, Tn, Tv and Td.
Change the value with
or .
Single figures can be selected by pressing
or .
Confirm your choice with the enter key
.
By pressing
(ESC) you are returned to the menu level without any change.
ESC
OK
Standby
Intern Pt100
Xp 10.0
Tn 30
Tv manual/auto auto
Tv 24(auto)
Tv 4(auto)
ESC
OK
- - -
Xp
Max: 30
Min: 0.1
10.0