Power supplies
Figure120.Redundantpowerinformationlabel
Replacingahot-swapdcpowersupply
Usethisinformationtoreplaceahot-swapdcpowersupply.
Thefollowingnotesdescribethetypeofpowersupplythattheserversupportsandotherinformationthat
youmustconsiderwhenyouinstallapowersupply:
Beforeyouinstallanadditionalpowersupplyorreplaceapowersupplywithoneofadifferentwattage,
youmayusethePowerConfiguratorutilitytodeterminecurrentsystempowerconsumption.For
moreinformationandtodownloadtheutility,gotohttp://www-03.ibm.com/systems/bladecenter/
resources/powerconfig.html.
Theservercomeswithonehot-swap12-voltoutputpowersupplythatconnectstopowersupplybay1.
Theinputvoltageis-48Vdcor-60Vdcauto-sensing.
Beforeyouinstalladcpowersupplyintheserver,youmustremoveallacpowersupplies.Donotuse
bothacanddcpowersuppliesinthesameserver.Installuptotwodcpowersuppliesoruptotwoac
powersupplies,butnotacombination.
Powersupply1isthedefault/primarypowersupply.Ifpowersupply1fails,youmustreplacethepower
supplywiththesamewattageimmediately.
Youcanorderanoptionalpowersupplyforredundancy.
Thesepowersuppliesaredesignedforparalleloperation.Intheeventofapower-supplyfailure,the
redundantpowersupplycontinuestopowerthesystem.Theserversupportsamaximumoftwo
powersupplies.
Itisthecustomer'sresponsibilitytosupplythenecessarypowercable.Toreducetheriskofelectric
shockorenergyhazards:
Useapropercircuitbreaker.
Use4mm
2
(10AWG)at90°Ccopperwire.
T orquethewiring-terminalscrewsto0.50~0.60newton-meters(4.43~5.31inch-pounds).
Formoreinformation,seeStatement34below.
Ifthepowersourcerequiresringterminals,youmustuseacrimpingtooltoinstalltheringterminalsto
thepowercordwires.TheringterminalsmustbeULapprovedandmustaccommodatethewirethatis
describedintheabove-mentionednote.