EasyManua.ls Logo

Lenze 8400 protec - Control Cables

Lenze 8400 protec
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation − EMS version
Installation according to EMC (installation of a CE−typical drive system)
Control cables
7
114
EDS84DPS424 EN 5.0
7.4.3 Control cables
ƒ Control cables must be shielded to minimise interference injections.
ƒ For lengths of 200 mm and more, use only shielded cables for analog and digital
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.
ƒ Connect the shield correctly:
The shield connections of the control cables must be at a distance of at least 50
mm from the shield connections of the motor cables and DC cables.
Connect the shield of digital input and output cables at both ends.
Connect the shield of analog input and output cables at one end (at the drive
controller).
ƒ To achieve an optimum shielding effect (in case of very long cables, with high
interference) one shield end of analog input and output cables can be connected to
PE potential via a capacitor (e.g. 10 nF/250 V) (see sketch).
9300vec043
Fig. 7−2 Shielding of long, analog control cables

Table of Contents

Related product manuals