Technical data
Control terminals
Digital outputs
4
65
EDS84DPS424 EN 5.0
4.7.2 Digital outputs
X42 − configured
Labelling Features Rated value
4 / DO1
2 / DO2
3 / GIO
Digital output
According to IEC61131−2, type 1
External−voltage protected up to +30 V
Integrated polarity reversal protection diode for
switching inductive loads
Isolation 76
Level LOW < +5 V
High > +15 V
Time−dependent behaviour LOW − HIGH / HIGH − LOW
max. 250 s
Behaviour during overload Reduced voltage or periodic switch−off/on
Behaviour in case of reset and during
switch−on
Outputs are switched−off (LOW)
Cycle time 1 ms
Max. output current 200 mA per output
1 / 24O
3 / GIO
24 V supply of the external sensors or
potential−free contacts
External supply at 24E: Voltage drop < 2.5 V
Total current for X4x, X50/X8x 1 A
Extensions in the EMS version
X46 − configured
Labelling Features Rated value
4 / DO3
2 / DO4
3 / GIO
Digital output
According to IEC61131−2, type 1
External−voltage protected up to +30 V
Integrated polarity reversal protection diode for
switching inductive loads
Isolation 76
Level LOW < +5 V
High > +15 V
Time−dependent behaviour LOW − HIGH / HIGH − LOW
max. 250 s
Behaviour during overload Reduced voltage or periodic switch−off/on
Behaviour in case of reset and during
switch−on
Outputs are switched−off (LOW)
Cycle time 1 ms
Max. output current 200 mA per output
1 / 24O
3 / GIO
24 V supply of the external sensors or
potential−free contacts
External supply at 24E: Voltage drop < 2.5 V
Total current for X4x, X50/X8x 1 A