7.6.2 Digital inputs and outputs
Note!
The maximum total current of the 24 V voltage supply for external actuators
and encoders is 1 A, e.g. ports
ƒ Digital inputs/outputs at X4x,
ƒ Analog input at X50 or SSI at X80, and
ƒ Serial interfaces RS485/RS422 at X81/X82.
Digital inputs
X41 − digital inputs DI1, DI2
Pin Signal Description Data
Type M12, 5−pole sockets
84DPSO05_5
1 24O 24 V supply of the external sensors
2 DI2 Digital input 2 According to IEC61131−2, type 1
or
Two−track frequency input for HTL
encoder 0 ... 100 kHz
3 GIO Reference potential HIGH
LOW
+15 .... +30 V DC
0 ... +5 V
4
DI1 Digital input 1 8 mA at 24 V DC
5 n. c. Not assigned
X42 − digital inputs DI3, DI4
Pin Signal Description Data
Type M12, 5−pole sockets
84DPSO05_5
1 24O 24 V supply of the external sensors
2 DI4
(DO2)
Digital input 4
(also available as digital output)
HIGH +15 .... +30 V DC
3 GIO Reference potential LOW 0 ... +5 V
4 DI3
(DO1)
Digital input 3
(also available as digital output)
8 mA at 24 V DC
5 n. c. Not assigned

Table of Contents