Diagnostics
Display of operating data, diagnostics
Status display of the safety system via LEDs at the controller
10
162
EDS84DPS424 EN 5.0
Pos. Colour State Description
DI7 yellow
on DI7 = HIGH
off DI7 = LOW
DI8 yellow
on DI8 = HIGH
off DI8 = LOW
DI9/DO3 yellow
on DI9/DO3 = HIGH
off DI9/DO3 = LOW
DI10/DO4 yellow
on DI10/DO4 = HIGH
off DI10/DO4 = LOW
DI11 yellow
on DI11 = HIGH
off DI11 = LOW
DI12 yellow
on DI12 = HIGH
off DI12 = LOW
DI13 yellow
on DI13 = HIGH
off DI13 = LOW
DI14 yellow
on DI14 = HIGH
off DI14 = LOW
10.1.3 Status display of the safety system via LEDs at the controller
Status display: drive−based safety
Pos. Colour State Description
S−State green
on
Communication between standard device and safety system
is running
blinking Drive−based safety is in service status
off
Communication between standard device and safety system
is not possible
S−Error red
on Fault, trouble or warning
blinking
Drive−based safety is not accepted by the standard device
off Error−free operation
S−Acknw yellow on A parameter set acceptance must be acknowledged
S−Enable yellow
on Controller is enabled
blinking Safety function is active (non−safe display)
The status of safety option 10 is solely shown via the "S−Enable" display. All other displays have no function.
Danger!
Danger to life due to wrong interpretation of the status display
A wrong interpretation of the status display of the drive−based safety may
result in dangerous operating statuses.
Possible consequences:
ƒ Death or severe injuries
Protective measures:
ƒ The status display of the drive−based safety must not be used for
safety−related purposes. The displays shown are unsafe.

Table of Contents