Electrical installation − HighLine/StateLine version
Important notes
Maximum motor cable length
6
77
EDS84DPS424 EN 5.0
6.1.3 Maximum motor cable length
ƒ Keep the motor cable as short as possible since this has a positive effect on the drive
behaviour.
ƒ The maximally permissible motor cable length is: 20 m, shielded
at rated mains voltage
at a switching frequency of 8 kHz
Note!
If the conditions for electromagnetic compatibility must be observed, the
permissible cable lengths may vary.
6.1.4 Motor protection
ƒ Extensive protection against overload:
By overcurrent relays or temperature monitoring.
We recommend the use of PTC thermistors or thermostats to monitor the motor
temperature.
PTC thermistors or thermostats can be connected to the controller.
For monitoring the motor, we recommend the use of the I
2
xt monitoring.
ƒ Only use motors with an insulation suitable for the inverter operation:
Insulation resistance: min. û = 1.5 kV, min. du/dt = 5 kV/s
When using motors with an unknown insulation resistance, please contact your
motor supplier.