Electrical installation − HighLine/StateLine version
Control terminals
Analog input
6
93
EDS84DPS424 EN 5.0
6.6.2 Analog input
The analog input can be used either as voltage input or as current input.
X50− analog inputs AI, AU
Pin Signal Description Data
Type M12, 5−pole sockets
84DPSO05_5
1 24O 24 V supply of the external sensors
2 AI Current input 0 ... +20 mA
4 ... +20 mA
3 GA Reference potential
4 AU Voltage input 0 ... 10 V
5 Controller 10 V reference voltage (output) + 10 V, max. 10 mA