Electrical installation − HighLine/StateLine version
Installation according to EMC (installation of a CE−typical drive system)
Shielding
6
80
EDS84DPS424 EN 5.0
6.4 Installation according to EMC (installation of a CE−typical drive system)
Design of the cables
ƒ It is imperative to comply with the regulations concerning minimum cross−sections
of PE conductors. The cross−section of the PE conductor must be at least as large as
the cross−section of the power connections.
ƒ The cables used must comply with the approvals required for the location (e.g. UL).
6.4.1 Shielding
Requirements
ƒ The effectiveness of a shielded cable is reached by:
Providing a good shield connection through large−surface shield contact.
Using only braided shields with low shield resistance made of tin−plated or
nickel−plated copper braid.
Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ Motor
ƒ External brake resistor ( Mounting Instructions of the brake resistor)
ƒ Motor holding brake (shielding is required when being integrated into the motor
cable; connection to optional motor brake control)
ƒ Motor temperature monitoring
ƒ Analog signals (inputs and outputs; single−sided shield connection to the controller)
ƒ Fieldbus communication (e.g. CANopen ,PROFIBUS, PROFINET, ...)
ƒ Safety system
ƒ CAN on board
The following connections need not be shielded:
ƒ Mains
ƒ 24−V supply
ƒ Digital signals (inputs and outputs).
We recommend to use shielded cables for a cable length from approximately 5 m
on or in environments with strong interferences.
Connection system
ƒ Directly apply the shielding in the plug.
Extensively apply the shielding and ensure electrical conductivity.
If required, additionally connect the shield to the cable clamp rail.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 protec and is the answer not in the manual?

Lenze 8400 protec Specifications

General IconGeneral
CategoryDC Drives
Series8400 protec
Protection ClassIP65
Control Modevector control
Communication InterfacesCANopen, PROFIBUS, PROFINET, EtherCAT, Ethernet/IP
Protection FeaturesOvercurrent, overvoltage, overtemperature
Relative Humidity5% to 95% (non-condensing)
Ambient Temperature-10°C to +45°C
Storage Temperature-25°C to +70°C

Related product manuals