Electrical installation − HighLine/StateLine version
Important notes
Electrical isolation
6
76
EDS84DPS424 EN 5.0
6.1.1 Electrical isolation
The protective insulation of the "8400 Inverter Drives" controllers is implemented
according to EN 61800−5−1. The following illustration shows the insulation concept.
X10
X11
X20
X21
X21
X3x
X4x
X50
X70
X80X6x
X10
X11
(24 V)
(24 V)
(T1/T2)

X22
X20
(T1/T2)
E84DWPT005
Fig. 6−1 Electrical isolation between power terminals, control terminals and housing
Isolation by functional insulation
I
Isolation by basic insulation
II
Safe isolation by double or reinforced insulation
Protection against accidental contact is guaranteed without any further
measures.
Power connections
X10, X11 Mains
X21 Motor
X20 Brake resistor
Control terminals
X10 (24 V)
X11 (24 V)
24 V supply voltage
X20 (T1/T2) brake resistor temperature monitoring
X21 (T1/T2) Motor temperature monitoring
X22 Voltage supply of external fan − only for 7.5 kW devices
X3x Fieldbus communication
X4x Digital inputs/outputs
X50 Analog input
X6x Safety system
X70 Diagnostics
X80 SSI
6.1.2 Device protection
ƒ In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.
ƒ The controller must be protected by external fuses.
ƒ Unused control inputs and outputs must be closed according to the intended type of
protection.