Technical data
Rated data
Overview
4
46
EDS84DPS424 EN 5.0
4.2 Rated data
4.2.1 Overview
Basis of the data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f [Hz]
3/PE AC 400 320 − 0 % ... 440 + 0 % 45 − 0 % ... 65 + 0 %
3/PE AC 500 400 − 0 % ... 550 + 0 % 45 − 0 % ... 65 + 0 %
Output switching frequency f = 4 kHz
Input data
Voltage Frequency Rated current [A]
Number of
phases
[V] [Hz] up to +45 °C up to +55 °C
E84Dxxxx7514 400/500 50/60 4.1/3.2 3.0/2.4 3
E84Dxxxx1524 400/500 50/60 5.5/4.4 3.5/3.1 3
E84Dxxxx3024 400/500 50/60 9.7/7.9 7.3/6.0 3
E84Dxxxx4024 400/500 50/60 12.9/11.0 9.5/8.1 3
E84DHxxx7524 400/500 50/60 20.8/16.6 15.6/12.5 3
Ambient temperature during operation
Rated data of the 24−V buffer voltage (preserves the control functionality in the event of
a mains failure):
Supply voltage for control electronics of the controller
(safely separated power supply unit SELV/PELV)
Typ Voltage range U
DC
[V DC] Current consumption at + 24 V DC [A]
Min.
1)
Max.
2)
E84Dxxxx7514
+ 24
(+19.2 − 0 % ... +28.8 + 0 %)
0.2 ... 0.6 2
E84Dxxxx1524
E84Dxxxx3024
E84Dxxxx4024
E84DHxxx7524
1)
according to optional equipment, digital inputs and outputs are not wired
2)
digital inputs and outputs are completely wired
Note!
The maximum total current of the 24 V voltage supply for external actuators
and encoders is 1 A, e.g. ports
ƒ Digital inputs/outputs at X4x,
ƒ Analog input at X50 or SSI at X80, and
ƒ Serial interfaces RS485/RS422 at X81/X82.