4×analog input / output
5
The modular system
5.12
l
5.12-2
EDSPM-TXXX-3.0-04/2004
AI/AO 2/2x12BIT
+0
M0
+1
M1
Q0
M0
Q1
M1
F
L+
L
EPM – T330 1A. 10
0
1
1
2
3
4
5
6
7
8
9
10
2
.
D
A
D
A
µP
2
1
3
5
7
9
10
4
6
8
PES
PES
PES
PES
PES
PES
PES
PES
–
+
DC 24 V
(DC 20.4
… 28.8 V)
MUX
D
A
epm-t127 epm-t123
Fig. 5.12-2 Front view and connection of 4×analog input / output
Status display L+; LED (yellow) is lit
Terminal strip assignment details
when a supply voltage is applied
1 DC 24 V supply voltage
Status display F; LED (red) is lit in
2 + analog input E.0
case of the following faults:
3 - analog input E.0
No external supply voltage
4 + analog input E.1
Wire breakage in the current
5 - analog input E.1
measu
in
an
e
6 Analog output A.0
7 GND (reference potential for
analog signals)
8 Analog output A.1
9 GND (reference potential for
analog signals)
10 GND (reference potential for
supply voltage)
)
Connection to backplane bus
Input resistorof actuator
Sensor (voltage or current source)
PES HF shield termination through
large-surface connection to PE
Note!
z
Short-circuit unused inputs (connect positive and negative
terminals) or deactivate them by assigning the function number
FF
h
.
z
Ensure correct polarity when connecting the actuators.
z
Unused outputs remain unassigned.
z
The 4×analog input/output module does not supply any
auxiliary voltage for sensors/actuators. For information on how
to connect sensors/actuators requiring auxiliary voltage, please
refer to the relevant sensor/actuator documentation.
Status display and terminal