MI 3102(H) BT EurotestXE Appendix A Fuse table
105
Fuse type gG
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
5
Min. prospective short- circuit current (A)
2
32.5
22.3
18.7
15.9
9.1
4
65.6
46.4
38.8
31.9
18.7
6
102.8
70
56.5
46.4
26.7
10
165.8
115.3
96.5
80.7
46.4
13
193.1
144.8
117.9
100
56.2
16
206.9
150.8
126.1
107.4
66.3
20
276.8
204.2
170.8
145.5
86.7
25
361.3
257.5
215.4
180.2
109.3
32
539.1
361.5
307.9
271.7
159.1
35
618.1
453.2
374
308.7
169.5
40
694.2
464.2
381.4
319.1
190.1
50
919.2
640
545
464.2
266.9
63
1217.2
821.7
663.3
545
319.1
80
1567.2
1133.1
964.9
836.5
447.9
100
2075.3
1429
1195.4
1018
585.4
Fuse type B
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
5
Min. prospective short- circuit current (A)
6
30
30
30
30
30
10
50
50
50
50
50
13
65
65
65
65
65
15
75
75
75
75
75
16
80
80
80
80
80
20
100
100
100
100
100
25
125
125
125
125
125
32
160
160
160
160
160
40
200
200
200
200
200
50
250
250
250
250
250
63
315
315
315
315
315