MI 3102(H) BT EurotestXE Technical specifications
91
10.4 RCD testing
10.4.1 General data
Nominal residual current (A, AC) ............ 10 mA, 30 mA, 100 mA, 300 mA, 500 mA,
1000 mA
Nominal residual current (EV, MI) ........... 30 mA a.c., 6 mA d.c.
Nominal residual current accuracy .......... -0 / +0.1I; I = IN, 2IN, 5IN
-0.1I / +0; I = 0.5IN
AS/NZS selected: ± 5 %
Test current shape .................................. Sine-wave (AC), pulsed (A, F), smooth DC (B, B+)
DC offset for pulsed test current ............. 6 mA (typical)
RCD type ................................................ (non-delayed), S (time-delayed), PRCD, PRCD-K,
PRCD-S, EV RCD, MI RCD
Test current starting polarity .................. 0º or 180º
Voltage range ......................................... 93 V 134 V (45 Hz 65 Hz)
185 V 266 V (45 Hz 65 Hz)
n.a. ......................................................... not applicable
............................................................. applicable
AC type................................................... sine wave test current
A, F types…… ........................................ pulsed current
B, B+ types ............................................. smooth DC current (MI 3102 BT only)
n.a. ......................................................... not applicable
............................................................. applicable
EV, MI type (a.c. part). ........................... sine wave test current
EV, MI type (d.c. part) ............................. smooth DC current