MI 3102(H) BT EurotestXE Technical specifications
98
10.9 Voltage, frequency, and phase rotation
10.9.1 Phase rotation
Nominal system voltage range ............... 100 V
AC
550 V
AC
Nominal frequency range ....................... 14 Hz 500 Hz
Result displayed .................................... 1.2.3 or 3.2.1
10.9.2 Voltage
(2 % of reading + 2 digits)
Result type ............................................ True r.m.s. (TRMS)
Nominal frequency range ....................... 0 Hz, 14 Hz 500 Hz
10.9.3 Frequency
(0.2 % of reading + 1 digit)
Nominal voltage range ........................... 10 V 550 V
10.9.4 Online terminal voltage monitor
(2 % of reading + 2 digits)