MI 3102(H) BT EurotestXE Technical specifications
90
10.2 Diagnostic test (MI 3102H BT only)
Dielectric absorption ratio DAR*
(5% of reading + 2digits)
* Only for test voltages 500 V
DC
, 1000 V
DC
and 2500V
DC
. If any insulation resistance values
(R
ISO
(15s) or R
ISO
(60s )) are over-ranged the DAR factor is not calculated. The result field is
blank: DAR:_____!
Polarization index PI**
(5% of reading + 2digits)
** Only for test voltages 500 V
DC
, 1000 V
DC
and 2500V
DC
. If any insulation resistance values
(R
ISO
(60s) or R
ISO
(10min)) are over-ranged the PI factor is not calculated. The result field is
blank: PI :_____!
10.3 Continuity
10.3.1 Resistance R LOW
Measuring range according to EN 61557 is 0.16 1999 .
(3 % of reading + 3 digits)
Measuring range R+, R- ()
(5 % of reading + 5 digits)
Open-circuit voltage ................................ 6.5 VDC 9 VDC
Measuring current ................................... min. 200 mA into load resistance of 2
Test lead compensation .......................... up to 5
The number of possible tests .................. > 2000, with a fully charged battery
Automatic polarity reversal of the test voltage.
10.3.2 Resistance CONTINUITY
(5 % of reading + 3 digits)
Open-circuit voltage ................................ 6.5 VDC 9 VDC
Short-circuit current ................................ max. 8.5 mA
Test lead compensation .......................... up to 5